If you want to measure the level of a liquid easily and reliably, a lot of people can do this using hydrostatic pressure measurement, e.g. with a submersible pressure transmitter or perhaps a so called level probe. The characteristic submersed application implicates a maximum exposure to the encompassing, mainly water-based medium, respectively to ?moisture?.
Exposure is not only limited by the wetted parts of the pressure sensor housing, but additionally to the entire immersed length of the cable. Furthermore, beyond your directly immersed level probe parts, the cable, and specifically the cable end, are often exposed to moisture as a result of splash water, rain and condensation. This is true not only during operation, but a lot more during installation and commissioning, or when maintenance or retrofitting is required. Irrespective of the prospective application, whether in water and wastewater treatment or in tank monitoring, moisture ingress into the cable ends of the submersible pressure transmitter can occur early and irreversibly with insufficient protection measures, and, in virtually all cases, result in premature failure of the instrument.
The ingress of moisture in to the cable outlet and from there on downwards into the electronics of the level probe must be actively eliminated by preventive actions by the user. To gauge the level with highest accuracy, the varying ambient pressure above the liquid media, which is also ?resting? on the liquid, must be compensated against the hydrostatic pressure acting on the pressure sensor (see article: hydrostatic level measurement).
Ventilation tube
Thus, it really is logical that there surely is a constant threat of a moisture-related failure because of moisture ingress (both via the ventilation tube and through the actual cable itself) if there are no adequate precautionary measures. To pay the ambient pressure ?resting? on the media, a ventilation tube runs from the sensor element within the particular level probe, through the cable and out of your level probe at the end of the cable. Because of capillary action within the ventialation tube useful for ambient pressure compensation, moisture can even be transported from the encompassing ambience down to the sensor.
Thus not only air, but additionally moisture penetrates into the tube, hence the sensor inside the probe and the electronics around it could be irreparably damaged. This can result in measurement errors and, in the worst case, even to failure of the level probe. To prevent any premature failure, the ingress of moisture into the ventilation tube should be completely prevented. Additional protection against moisture penetration through the ventilation tube is supplied by fitting an air-permeable, but water-impermeable filter element at the end of the vent tube.
bare wires
Not to be ignored can be the transport of the liquid through high-humidity loads across the only limitedly protected internals of the cable, e.g. along the wires, all the way down to the submersible pressure transmitter. As a respected manufacturer, WIKA uses appropriate structural design to avoid fluid transport, as far as possible, in to the electronics of the submersible pressure transmitter. Due to molecular diffusion and capillary effects, a guaranteed one-hundred percent protection on the full lifetime of the submersible pressure transmitter, however, is never achievable.
Hence, it is recommended that the cable is always terminated in a waterproof junction box with the appropriate IP protection (e.g. IP65) that is matched to the installation location. If this cable junction box is exposed to weather and varying temperature conditions, it is also recommended to pay focus on a controlled pressure equalisation to be able to prevent the formation of condensation or perspiration water and pumping effects. To address this technical requirement, as an accessory to a submersible pressure transmitter, you’ll be able to order a link box having an integrated air-permeable, water-impermeable membrane.
Ultimately, moisture ingress can happen not only through the exposed end of the cable, but additionally through mechanical damage to the cable sheath or because of liquid diffusion because of improper chemical resistance of the cable material. In this article ?Selection criteria for preventing moisture-related failures of submersible pressure transmitters or level probes? Child-like is described in detail.
WIKA offers comprehensive solutions for the hydrostatic-pressure level measurement. For further assistance in selecting the submersible pressure transmitter the most suitable for the application, please use our contact form.
Please find further information with this topic on our information platform ?Hydrostatic level measurement?