Differential pressure measurement is trusted as a way for monitoring the amount of closed vessels. Oftentimes, operators use individual instruments with an output signal or on-site display. On the other hand, a far more precise and fault-immune solution is the measuring arrangement developed by WIKA using two process transmitters in a primary-secondary relationship.
เกวัดแรงดันน้ำ monitoring application using differential pressure measurement is founded on the following principle: For the amount of the contents in the vessel, the differential pressure between your liquid and the gaseous phase is set. In addition, the hydrostatic pressure, the specific density of the medium and the vessel geometry are contained in the calculation. Typical measuring instruments have two adjacent process connections for the pressures P1 and P2. For level measurement, a capillary has to bridge the pronounced distance between the two measuring points.
Measurement with two process transmitters as Primary instrument (right) and Secondary instrument. This measuring arrangement for level monitoring can be used flexibly, e.g. for info on the mixing ratio of liquids.
Connection via signal cable
When monitoring the level using electronic differential pressure measurement, alternatively, both measuring points have one process transmitter each. For instance, the WIKA models CPT-2x and IPT-2x are suitable for this. The two transmitters are arranged as Primary instrument and Secondary instrument. They’re connected, purely electrically, via a signal cable and so are therefore not susceptible to disturbances. The Primary instrument supplies the Secondary instrument with power. The Secondary instrument is parameterised with a serial interface or through the display on the principal instrument. Finally, communication occurs via an interior bus.
Level monitoring in a closed tank
Application example
The figure on the left shows a typical application example for level monitoring with electronic differential pressure measurement on a liquid tank. The Secondary instrument measures the pressure P1, in this case the gas pressure, and transmits it to the Primary instrument. This detects the pressure P2, here the pressure in the liquid column in the bottom of the tank. THE PRINCIPAL instrument calculates the differential pressure from P1 and P2. Utilizing the measured value and considering the other parameters mentioned, it determines the volume in the tank being an indication of the particular level. This value can be output either as an analogue or digital signal to the control room and/or to the display of the Primary instrument.
Benefits of the measuring arrangement with two process transmitters
The technique for level monitoring described here has several advantages when compared to a conventional method, for instance, with a differential pressure transmitter:
Higher accuracy and ?turndown?
Process transmitters deliver higher degrees of accuracy. Regarding the WIKA models, they are up to 0.05 % of the set span. Furthermore, there is the possibility of ?turndown?, the average person setting of a specific measuring span (that is also possible retrospectively with instruments that are already installed.)
Minimised temperature effect
Transmission via signal cable with electronic differential pressure measurement minimises the temperature effect. On the other hand, the capillaries used in the conventional measuring method are a lot more susceptible here. This, subsequently, can ultimately affect the measuring result.
Fast commissioning
The electronic measuring arrangement can be commissioned faster. Contrary to a solution with capillaries, it does not require any test run.
Reduced maintenance effort
The maintenance effort is lower: In case of a fault, only the process transmitter concerned needs to be replaced. In contrast, with measuring differential pressure with capillaries, the complete measuring arrangement should be replaced.
Note
More info on the model CPT-2x and IPT-2x process transmitters, which are suitable for electronic differential pressure measurement for level monitoring, can be acquired on the WIKA website.